ebook img

Commissioning Code A: Air Distribution Systems PDF

43 Pages·1996·0.894 MB·English
by  CIBSE
Save to my drive
Quick download
Download
Most books are stored in the elastic cloud where traffic is expensive. For this reason, we have a limit on daily download.

Preview Commissioning Code A: Air Distribution Systems

Air distribution systems CIBSE Commissioning Code A: 1996 (2004) The rights of publication or translation are reserved. Nopart of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means without the prior permission of the Institution. This edition first published August 1996; reviewed and confirmed August 2004. ©August 2004 The Chartered Institution of Building Services Engineers London ISBN0 900953 73 X This document is based on the best knowledge available at the time of publication. However no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of these recommendations can be accepted by the Chartered Institution of Building Services Engineers, the authors or others involved in its publication. In adopting these recommendations for use each adopter by doing so agrees to accept full responsibility for any personal injury, death, loss, damage or delay arising out of or in connection with their use by or on behalf of such adopter irrespective of the cause or reason therefore and agrees to defend, indemnify and hold harmless the Chartered Institution of Building Services Engineers, the authors and others involved in their publication from any and all liability arising out of or in connection with such use as aforesaid and irrespective of any negligence on the part of those indemnified. Typeset by CIBSE Publications Department Printed in Great Britain by Hobbs the Printers Ltd., Totton, Hampshire, SO40 3WX Note from the publisher This publication is primarily intended to provide guidance to those responsible for the design, installation, commissioning, operation and maintenance of building services. It is not intended to be exhaustive or definitive and it will be necessary for users of the guidance given to exercise their own professional judgement when deciding whether to abide by or depart from it. Appendices 19 AA1 Design implications 19 AA1.1 Introduction 19 AA1.2 Design requirement 19 AA1.3 Design information 20 AA1.4 Design development considerations 20 AA2 Installation 22 AA2.1 Introduction 22 AA2.2 Requirements 22 AA2.3 Cleanliness 22 AA2.4 Inspections 22 AA2.5 Ductwork leakage testing 22 AA2.6 Static completion certificate 23 AA3 Measurement of air flow and calibration of instrumentation 23 AA3.1 Equipment, instruments and measuring techniques for 23 typical procedures AA3.2 Instrument calibration 23 AA3.3 Comparison of two or more methods of measurement 23 AA3.4 Tolerances for regulation of air flow 23 AA4 Health and safety arrangements 24 AA4.1 Introduction 24 AA4.2 Contractor’s duties 24 Index 26 List of figures and table Figure 1Key stages involved in the commissioning of air 1 distribution systems Figure 2Flow chart for activities prior to proportional balancing 6 Figure 3Air distribution junction 7 Figure 4A typical branch duct configuration 7 Figure 5A typical air distribution system 8 Figure 6Flow chart for proportional balancing and testing of 12 air systems Figure 7Flow chart for commissioning of VAVsystems 14 Figure 8Flow chart for commissioning of typical ventilation systems 17 designed to produce pressure regimes within a space Table A1Cumulative tolerance limits for regulation of air flow 24 Contents A0 Introduction 1 A0.1 Scope 1 A0.2 Definitions 1 A0.3 Commissioning method statements 2 A0.4 Specification 3 A0.5 Inspection and testing 3 A0.6 Commissioning records 3 A0.7 Responsibility 3 A0.8 Practical considerations 3 A1 Preliminary checks 3 A1.1 Objective 3 A1.2 State of the building and system 3 A1.3 System cleanliness 3 A1.4 Air regulating devices and other components within airways 4 A1.5 Visual checks for air tightness 4 A1.6 Fan checks 4 A1.7 Electrical checks 4 A2 Setting to work 5 A2.1 Procedure 5 A2.2 Preliminary checks 5 A2.3 Precautions against airborne detritus 5 A2.4 Precautions against frost 5 A2.5 Initial running of fan set 5 A3 Regulation of air flow 6 A3.1 Principles 6 A3.2 Procedures 7 A3.3 Techniques 10 A3.4 Variable air volume systems 13 A3.5 Pressure regimes 16 A4 Commissioning documentation 17 A4.1 Content 17 A4.2 Format 18 A5 Witnessing 18 A5.1 Introduction 18 A5.2 Objective 18 A5.3 Selection of the witnessing authority 18 A5.4 Programme 18 A5.5 General 18 A5.6 Witnessing arrangements 19 A5.7 Air distribution system acceptance 19 Appendices 19 AA1 Design implications 19 AA1.1 Introduction 19 AA1.2 Design requirement 19 AA1.3 Design information 20 AA1.4 Design development considerations 20 AA2 Installation 22 AA2.1 Introduction 22 AA2.2 Requirements 22 AA2.3 Cleanliness 22 AA2.4 Inspections 22 AA2.5 Ductwork leakage testing 22 AA2.6 Static completion certificate 23 AA3 Measurement of air flow and calibration of instrumentation 23 AA3.1 Equipment, instruments and measuring techniques for 23 typical procedures AA3.2 Instrument calibration 23 AA3.3 Comparison of two or more methods of measurement 23 AA3.4 Tolerances for regulation of air flow 23 AA4 Health and safety arrangements 24 AA4.1 Introduction 24 AA4.2 Contractor’s duties 24 Index 26 List of figures and table Figure 1Key stages involved in the commissioning of air 1 distribution systems Figure 2Flow chart for activities prior to proportional balancing 6 Figure 3Air distribution junction 7 Figure 4A typical branch duct configuration 7 Figure 5A typical air distribution system 8 Figure 6Flow chart for proportional balancing and testing of 12 air systems Figure 7Flow chart for commissioning of VAVsystems 14 Figure 8Flow chart for commissioning of typical ventilation systems 17 designed to produce pressure regimes within a space Table A1Cumulative tolerance limits for regulation of air flow 24 1 Air distribution systems A0 Introduction A0.2 Definitions For the purpose of this Code the following definitions A0.1 Scope apply. This Code deals with the work stages required to commis- Accuracy sion typical air distribution systems. The procedures represent a standard of good practice generally accepted in the building engineering services industry and are, there- Accuracy is a compounding of the following factors: fore, presented in the form of recommendations and instrument accuracy, flow measuring device accuracy and guidance. operator accuracy. Refer to the BSRIA Application Guide 3/89.1: The commissioning of air systems in buildings(1) for The Code sets out generally to inform on ‘what should be further information. done’. Manuals published by the Building Services Research and Information Association (BSRIA) inform on Accuracy — flow measuring device ‘how it should be done’. The flow chart in Figure 1 illustrates the key stages invol- Variations in the reading arising from manufacturing ved in the commissioning of air distribution systems tolerances of the flow measuring device. covered by this Code. Attention is drawn to the fact that there are other, subsequent stages that do not form part of Accuracy — instrument this Code. Variations in the reading arising from manufacturing tolerances in the instrument. Planning and programme Accuracy — operator Method statements Any error introduced by the operator such as parallax in Static completion certified the reading of instruments or test points not ideally positioned. Setting to work Commissionable system Air volume flow rate regulation A system designed, installed and prepared to specified requirements in such a manner as to enable commissioning to be carried out. Fan performance testing Commissioning Witnessing The advancement of an installation from the state of static Air distribution system acceptance End of code A completion to full working order to specified require- ments. It includes the setting to work of an installation and regulation of the system flow rates. Systems proving Commissioning management Systems acceptance The planning, organisation, coordination and control of Environmental assessment commissioning activities. Commissioning manager Figure 1 Key stages involved in the commissioning of air distribution The firm or person appointed to manage the commission- systems ing process. 2 Air distribution systems Commissioning specialist Scan— final The firm or person appointed to carry out specified duties The final set of recorded measurements taken of a system in connection with commissioning. upon completion of the regulation process. Definitive air volume flow rate Scan — initial The inferred volume flow rate derived from measurements The first set of recorded measurements taken of a system taken using a pitot tube in accordance with defined tech- with all regulation devices in the fully open position prior niques. to any regulaton. Setting to work Design criteria The process of putting a static system into dynamic opera- The specified environmental conditions, fluid flow rates tion. and equipment outputs required to meet a particular design performance. Specification Diversity The document that prescribes the requirements for com- missioning by reference to drawings, information sche- A hypothetical aggregate simultaneous air volume flow dules and relevant codes, manuals, guides and standards. rate at design maximum system performance, compared with the summation of the design maximum air volume output of all terminal units. The diversity ratio is often Static completion quoted as a percentage. The state of a system installed in accordance with the specification, ready for ‘setting to work’. This includes Fine tuning cleaning and pressure leakage testing of the distribution system (where required). Local adjustment to the system where usage and system proving have shown a need for it. This may also include the re-assessment of control set points and values to System achieve optimum performance. A set of connected components for heating, cooling, venti- lation or air conditioning consisting of plant, distribution Hood ducting and terminal units together with arrangements to control their operation. A proprietary or custom-made device used to capture air flow from an air distribution terminal for the purposes of System proving measurement (flow or velocity). Measuring, recording, evaluating and reporting on the Index (terminal/sub-branch/branch) seasonal performance of a system against specified design criteria. The terminal/sub-branch/branch in a distribution system which, prior to regulation of air flow, receives the lowest Testing indicated percentage of design fluid flow rate. The measurement and recording of system parameters to Indicated air volume flow rate assess specification compliance. The inferred volume flow rate derived from Tolerance measurements, typically at terminal outlets, taken using proprietary instrumentation and devices (e.g. terminal air Permissible deviation from a specified design collection hoods). requirement. Pressure and leakage testing A0.3 Commissioning method The process of measuring and recording specified pressure statements retention or permitted rate of leakage in an air distribution system or component part thereof. To ensure that all technicians work to the same procedures and sequences, the commissioning specialist should compile a commissioning method statement Regulation particular to the project. This method statement should include particulars, in principle or in detail as appropriate, The process of adjusting volume flow rates of a fluid in a of the following: distribution system to achieve specified values (within tolerances). (a) equipment and instrumentation to be used Introduction 3 (b) preliminary checks to be applied (e.g. sections A0.8 Practical considerations A1.2 to A1.7) The measuring, regulating and apportioning of air flow in (c) commissioning procedures to be followed (e.g. a distribution system as applied in the commissioning sections A2 and A3) procedures described in this Code is a means to an end. The primary objective is to ensure that the performance of (d) tolerancesto be applied in air flow regulation the commissioned installation is adequate to maintain the specified space environmental conditions with optimum (e) arrangements, where appropriate, for witnessing efficiency. (e.g. the advance notice to be given). It should be borne in mind that flow rate apportionment In some instances, the commissioning specification may to unnecessarily close tolerances will result in high com- require the commissioning specialist to submit a method missioning costs, with little or no practical advantage. statement for approval. Where this is not a requirement, the Also, the use of additive tolerances (e.g. –0% +10%) could commissioning specialist may nonetheless wish to make a result in running cost penalties throughout the life of the formal submission of a particular method statement to the installation. It is the responsibility of the designer to contractor/client. By this means, interested parties would specify flow rate tolerances and to ensure that these are be informed of the commissioning intent, thus providing appropriate to the particular design, installation and scope for any concerns regarding methods or procedures to application. be addressed before commissioning is commenced. A0.4 Specification A1 Preliminary checks The Code assumes that the installation is complete and properly constructed to an agreed specification. The speci- A1.1 Objective fication should state permissible tolerances within which the system should operate. The purpose of the procedure given in this section is to check that the system is in a satisfactory and safe condition before starting up. All the following checks A0.5 Inspectionand testing should be carried out in the sequence given before the initial running of fans. The requirements of this Code do not replace the need for regular inspection of the installation which should be A1.2 State of the building and system carried out during construction. All ductwork and mech- anical and electrical plant should be tested as required by Before starting regulation it is essential that the following the specification and the test results recorded and docu- conditions are fulfilled: mented. Testing carried out in accordance with the requirements of the specification, both on and off site, (a) the building is complete and windows and doors should be recorded and the documents made available to are open or shut consistent with their normal state the commissioning specialist prior to the commencement (see section A3.5 when dealing with pressure of their works. related areas e.g. laboratories, operating theatres etc.) (b) the air distribution system is complete and, where A0.6 Commissioning records required by the specification, leakage testing is satisfactorily concluded, inclusive of builders’ It is essential that all checks and measurements are work ducts and shafts recorded in writing at the time they are made. Breaks in the continuity of commissioning operations are likely, and (c) the requirements of this section, sections A1.3– proper records will show the state of progress at any stage. A1.7 and A2.2–A2.5 have been met It is most important that commissioning records are (d) all main and branch heaters and coolers on supply provided as part of the ‘hand-over’ documentation. It is systems are shut off to maintain consistent air den- recommended that a standardised format be agreed for sity during testing. However, in cold weather and recording the necessary commissioning performance data particularly on full outside air systems, some heat- for a particular project. ing may be applied to the main airstream (which handles the total air flow) in order to temper the air delivered by the system (see also section A2.4). A0.7 Responsibility A1.3 System cleanliness The responsibility for commissioning is a contractual matter outside the scope of this Code. Nevertheless, it is recommended that the managementof the whole commis- Note: it is important to ensure a reasonable standard of sioning process be under the guidance and control of a system cleanliness before start-up. Debris may be single authority. Total commissioning management may entrained by air flow on start-up, significantly reducing be considered as an option. the life of the filter media and other system components. Introduction 3 (b) preliminary checks to be applied (e.g. sections A0.8 Practical considerations A1.2 to A1.7) The measuring, regulating and apportioning of air flow in (c) commissioning procedures to be followed (e.g. a distribution system as applied in the commissioning sections A2 and A3) procedures described in this Code is a means to an end. The primary objective is to ensure that the performance of (d) tolerancesto be applied in air flow regulation the commissioned installation is adequate to maintain the specified space environmental conditions with optimum (e) arrangements, where appropriate, for witnessing efficiency. (e.g. the advance notice to be given). It should be borne in mind that flow rate apportionment In some instances, the commissioning specification may to unnecessarily close tolerances will result in high com- require the commissioning specialist to submit a method missioning costs, with little or no practical advantage. statement for approval. Where this is not a requirement, the Also, the use of additive tolerances (e.g. –0% +10%) could commissioning specialist may nonetheless wish to make a result in running cost penalties throughout the life of the formal submission of a particular method statement to the installation. It is the responsibility of the designer to contractor/client. By this means, interested parties would specify flow rate tolerances and to ensure that these are be informed of the commissioning intent, thus providing appropriate to the particular design, installation and scope for any concerns regarding methods or procedures to application. be addressed before commissioning is commenced. A0.4 Specification A1 Preliminary checks The Code assumes that the installation is complete and properly constructed to an agreed specification. The speci- A1.1 Objective fication should state permissible tolerances within which the system should operate. The purpose of the procedure given in this section is to check that the system is in a satisfactory and safe condition before starting up. All the following checks A0.5 Inspectionand testing should be carried out in the sequence given before the initial running of fans. The requirements of this Code do not replace the need for regular inspection of the installation which should be A1.2 State of the building and system carried out during construction. All ductwork and mech- anical and electrical plant should be tested as required by Before starting regulation it is essential that the following the specification and the test results recorded and docu- conditions are fulfilled: mented. Testing carried out in accordance with the requirements of the specification, both on and off site, (a) the building is complete and windows and doors should be recorded and the documents made available to are open or shut consistent with their normal state the commissioning specialist prior to the commencement (see section A3.5 when dealing with pressure of their works. related areas e.g. laboratories, operating theatres etc.) (b) the air distribution system is complete and, where A0.6 Commissioning records required by the specification, leakage testing is satisfactorily concluded, inclusive of builders’ It is essential that all checks and measurements are work ducts and shafts recorded in writing at the time they are made. Breaks in the continuity of commissioning operations are likely, and (c) the requirements of this section, sections A1.3– proper records will show the state of progress at any stage. A1.7 and A2.2–A2.5 have been met It is most important that commissioning records are (d) all main and branch heaters and coolers on supply provided as part of the ‘hand-over’ documentation. It is systems are shut off to maintain consistent air den- recommended that a standardised format be agreed for sity during testing. However, in cold weather and recording the necessary commissioning performance data particularly on full outside air systems, some heat- for a particular project. ing may be applied to the main airstream (which handles the total air flow) in order to temper the air delivered by the system (see also section A2.4). A0.7 Responsibility A1.3 System cleanliness The responsibility for commissioning is a contractual matter outside the scope of this Code. Nevertheless, it is recommended that the managementof the whole commis- Note: it is important to ensure a reasonable standard of sioning process be under the guidance and control of a system cleanliness before start-up. Debris may be single authority. Total commissioning management may entrained by air flow on start-up, significantly reducing be considered as an option. the life of the filter media and other system components. 4 Air distribution systems Prior to the fitting of filters, check the following for clean- (c) ductwork joints, including flexible couplings, are liness: air tight (a) air intake screens (d) inspection covers are fitted (b) fanand other equipment chambers (e) drainage trap water seals are intact (c) fan internals (f) plugs or covers for test holes are fitted. (d) heater and cooler batteries (e) cooling coil condensate trays A1.6 Fanchecks (f) condensate drainage traps The following should be checked: (g) eliminators (a) internal and external cleanliness (h) humidifiers (b) all components, bolts, fixings etc. are secure (i) volume control dampers and linkages (c) impeller secured, free to rotate, of correct handing (j) fire dampers and correct clearances (k) ducting and other airways (d) axial-flow-type fans installed for correct air flow direction and, where compounded, in correct order (l) sensing elements (e) anti-vibration mountings and the removal of tran- (m) terminal units. sit bolts and packing materials The commissioning specialist should formally report any (f) correct drive is fitted instances of unsatisfactory cleanliness to the appropriate (g) securing and alignment of pulleys and couplings level in the project management. (h) belt tension and match (i) where necessary, lubrication has been applied in A1.4 Air regulating devicesand other accordance with manufacturer’s requirements components within airways (j) drive guards fitted, access for speed measurement provided The following checks should be made: (k) where appropriate, satisfactory operation of inlet (a) turning vanes, thermal insulation, acoustic linings, guide vanes and variable pitch fans over full range battery fins and sensing elements have been fitted of movement. and are undamaged (b) heater and cooler batteries, humidifiers, filters, sil- A1.7 Electricalchecks encers etc. are installed correctly in relation to air flow Prior to the initial running of any electrically driven fan, (c) volume control dampers are operating electric air heater or automatically advancing filter, the (d) there is freedom of movement, throughout range, following procedures should be adopted: on motorised damper control linkages (e) dampers throughout the system are secured in the A1.7.1 With all electrical supplies isolated fully open position (except where other require- ments may be specified) Check: (f) there is free movement of fire dampers, together (a) local isolation of motorand control circuits with the location of, access to and fitting of fusible (b) no unshrouded live components within panels link assemblies; all fire dampers are finally secured in the open position (c) panels and switchgear clean (g) all adjustable louvres set without deflection, i.e. (d) motor and surrounding area clean; air heaters clean normal to face of grille; adjustable cones on dif- (e) transit packing removed from contactors and other fusers set either all in the fully up or all in the fully equipment down position (f) no mechanical damage to switchgear or air heaters (h) test holes are provided at strategic points for the measurement of branch and total air volume flow (g) all mechanical checks on fan, motor and automatic rates. filter complete (see section A1.6) (h) all connections tight on busbars and wiring A1.5 Visual checks for air tightness (i) internal links on starter correct (j) all power and control wiring completed in detail to Check to ensure that: the circuit diagram (special attention to circuits for (a) builders’ work ducts and shafts are sealed star-delta connected or specially wound motors) (b) plant access doors are sealed around whole periphery (k) fuse ratings correct

See more

The list of books you might like

Most books are stored in the elastic cloud where traffic is expensive. For this reason, we have a limit on daily download.