ebook img

(as) with biological aerated filter (baf) - Environmental Expert PDF

13 Pages·2006·0.37 MB·English
by  
Save to my drive
Quick download
Download
Most books are stored in the elastic cloud where traffic is expensive. For this reason, we have a limit on daily download.

Preview (as) with biological aerated filter (baf) - Environmental Expert

WEFTEC®.06 LONG TERM FULL SCALE COMPARISON OF ACTIVATED SLUDGE (AS) WITH BIOLOGICAL AERATED FILTER (BAF) Rene Hansen*, Torben. Thøgersen* and Frank Rogalla** *Public Works Department, Operation and Construction, DK-9900 Frederikshavn, Denmark **Black & Veatch, 69 London Road, Redhill, Surrey, UK RH 1 1 LQ ABSTRACT The Wastewater Treatment Plant (WWTP) of Frederikshavn, Denmark, was extended in the early nineties to increase its average daily flow to 4,5 MGD (16,500 m³/d) and meet new requirements for nutrient removal (8 mg/l TN, 1,5 mg TP/l). A parallel biological aerated filter (BAF) was the selected as the most economical upgrade of the existing activated sludge plant (AS), and started up in 1995. Running two full scale processes in parallel on the same wastewater and treatment objectives for over ten years enabled a direct comparison in relation to operating performance, costs and experience. After screening, a combined grit and grease chamber and 3 primary settlers, the effluent is pumped to the bio-treatment, consisting of AS with recirculation (Modified Lutzack-Ettinger – MLE) and an upflow BAF with floating media. The wastewater is a mixture of industrial and domestic wastewater, with a dominant discharge of fish processing effluent which can amount to 50 % of the flow. The maximum hydraulic load on the pretreatment section as a whole is 10 MGD (1,530 m3/h) . Approx. 60% of the sewer system is combined with a total of 32 overflow structures. To avoid the direct discharge of combined sewer overflows into the receiving waters, the total hydraulic capacity of the plant is increased during rain to 27 mgd (4,330 m³/hour) or 6 times average flow. During rain, this is achieved by directing some of the raw sewage through a stormwater bypass to the BAF and switching all six BAF to full nitrification. After final bio- treatment, the wastewater is conveyed through a 500 m sea outfall. The operation of the BAF can be modified to accommodate various treatment needs: - either using simultaneous nitrification/denitrification in all filters with recirculation - bottom aeration with full nitrification in all filters for stormwater treatment - or post-denitrification in 1 filter. On-line measurements for the parameters NO , NO , NH and PO as well as dissolved oxy- 3 2 4 4 gen (DO) are used for control of aeration and for addition of flocculants for P-removal and external carbon source (methanol). The BAF backwash sludge, approx. 0.5 MGD (1.900 m³/d) once every 24 h in dry weather, is redirected to the AS plant. Sludge from primary set- tlers and the combined biosolids from the AS plant are anaerobically digested, with methane gas being used for generation of heat and power. This paper discusses the experience gained from the plant operation during the last ten years, compiling comparative performance and cost data of the two processes. Copyright © 2006 Water Environment Foundation. All Rights Reserved 162 WEFTEC®.06 KEY WORDS Activated Sludge (AS); Biological Aerated Filter (BAF); Nitrogen removal, Control Strategy; Operating Costs; Operating Experience; Parallel Operation; Wet Weather Load, Combined Sewer Overflows (CSO) FREDERIKSHAVN WASTEWATER TREATMENT PLANT The Frederikshavn WWTP was originally a conventional activated sludge plant for secondary treatment. In the early nineties, to meet the demands of the Danish Action Plan on the Aquatic Environment, the plant went through an extensive upgrading to meet new effluent require- ments including total nitrogen removal. In 1995, a BAF unit was put in parallel operation with the existing activated sludge plant, in order to avoid the large additional aeration volume re- quired to reach nitrification. This unique configuration permitted comparable studies of the efficiency and operation of the two treatment processes on full scale. The WWTP has an av- erage capacity of 4.5 mgd (16,500 m³/24 h), or approx. 130,000 PE. The raw wastewater flows through a screen to the inlet well of the treatment plant. From here, the water is pumped to the pre-treatment section, which consists of an aerated grit and grease removal tank and 3 rectangular primary settlers. Ferric Chloride is added to the primary tanks to obtain phosphorus removal and reduce the size of the bioreactors. The maximum design flow on the pretreatment is 10 mgd (1,530 m3/h), a peak factor of 2,2 compared to the design average flow. The effluent gravitates from the primary settlers into a distribution chamber, to be divided between BAF and AS. During rain, some of the pretreated water can be directed through a stormwater bypass directly to the BAF. A plant flowscheme is shown in Fig. 1. The bio-treatment consists of an AS with pre-anoxic zone and internal recirculation. The parallel BAF also has an aerated zone in the top and an anoxic zone in the bottom, fed by the influent and recirculation. One BAF cell is used for post-denitrification polishing. All filters can also operate with bottom aeration with full nitrification in all filters, to handle storm flows. The backwash sludge liquor from the BAF is returned to the aeration basin of the AS. After final treatment in the biological section, the wastewater is conveyed to a discharge tower, from where it either flows or is pumped through a 500 m (1500 ft) sea outfall. Sludge from the primary settlers and the AS plant is stabilised in anaerobic digestion tanks, in which methane gas is produced and used for generation of heat and power. WASTEWATER COMPOSITION AND FLOW DISTRIBUTION Approx. 50% of the wastewater comes from the fish processing industry. The remaining 50% is a mixture of other industrial wastewater and domestic wastewater. The yearly average com- position of the wastewater after chemically enhanced primary settling for the last 10 years is shown in Fig. 2. Total COD averages around 250 mg/l, of which the soluble fraction is 50 %. BOD is close to 200 mg/l and TSS is slightly lower than 100 mg/l. Approx. 60% of the sewer system in Frederikshavn is combined. Before the extension of the biological treatment, a total of 32 overflow structures relieved the collection system of mixed Copyright © 2006 Water Environment Foundation. All Rights Reserved 163 WEFTEC®.06 stormwater and wastewater. To avoid the direct discharge into the receiving waters and the associated contamination in the coastal areas of the Kattegat Bay, an increased hydraulic load on the filters of the BAF was considered. By adjusting all six filters to full nitrification by applying the bottom aeration, a hydraulic capacity of 3,630 m³/h (23 mgd) could be obtained in the BAF with a surface load of 9.6 m³/m²/hour (4 gpm/ft2, Tschui et al., 1992). The inlet pumping station was reconstructed and a stormwater by-pass leading directly to the intake channel of the BAF was installed. The control systems in some of the most important pumping stations in the sewer system have been replaced to make on-line control of water level and pumping capacity possible. These data can be used for advance warning of the in- creased load on the wastewater treatment plant so that the BAF can be adjusted before the peak flows arrive: the filters are washed and changed from normal operation to stormwater operation, providing full nitrification and bottom aeration in all six filters. The total hydraulic capacity of the WWTP during rain is now 4,330 m³/hour (27 mgd), in- creasing its capacity to 6 times average dry weather flow and reducing the overflow to the receiving waters by approx. 70%. The environment, particularly along the stretches of coast to the immediate North and South of the WWTP, where anaerobic conditions occasionally caused severe odour complaints, has been sensibly improved by the new flow management. The flow occurrence in the treatment plant during the last ten years is illustrated in Fig.3. Whereas initially the wastewater was below the design flow of 16 500 m3/d (4.3 mgd), the average yearly flows were around 30 % higher in a wet period from 1999 to 2003. Conse- quently, the partial bypass of up to 20 % during peak wet weather flows had to be re- introduced after the first few years of operation. Fig 3 also shows the relative hydraulic load of BAF and AS: the latter receives around 80 % of the former, including about 20 % of back- wash flow from the BAF. The recirculation on the BAF is in the same order of magnitude, slightly higher than 80 % of its influent. The composition of the sludge liquor returned from the BAF to the AS varies according to the current mode of operation. In dry weather situations, the filters are washed once every 24 hours, which results in a total sludge liquor load of approx. 1,900 m³/d (0.5 mgd). The aver- age composition of the sludge liquor load in dry weather situations from the 5 filters with recirculation appears from table 1 below, showing that the backwash water has a moderated solids load (more than three times the primary settled value) and only a small amount of dis- solved pollution (low filtered COD, ammonia or phosphate). Table 1: Composition of the sludge liquor from BAF with recirculation COD 424 mg/l COD(f) 86 mg/l Total N 42 mg/l N-NO 4.5 mg/l 3 NH -N 5 mg/l PO -P 1 mg/l 4 4 Total P 12.4 mg/l SS 320 mg/l Copyright © 2006 Water Environment Foundation. All Rights Reserved 164 WEFTEC®.06 BIOLOGICAL TREATMENT The biological section of the treatment plant consists of AS and BAF, both with pre- denitrification and recirculation. General design characteristics of the AS system are: Max. hydraulic load from pretreatment: 700 m³/h 4.4 mgd Nitrification volume: 2,300 m³ 605 mgal Denitrification volume: 1,240 m³ 325 mgal Volume of clarifiers: 3,000 m³ 790 mgal Surface of clarifiers: 750 m² 8333 ft2 Max. surface load of clarifiers: 1,1 m³/m²/h 0.44 gpd/ft2 The equivalent design parameters for the BAF, where normally 5 filters are operated with recirculation (denitrification/nitrification) and 1 filter is used for post-denitrification, are: Max. hydraulic load from pretreatment: 830 m³/h 5.2 mgd Max. hydraulic capacity, wet weather: 3,600 m³/h 22.7 mgd Unitary Filter surface 63 m² 700 ft2 Nitrification volume (6 filters in recirculation) 794 m³ 29 400 ft3 Denitrification volume (6 filters in recirculation) 340 m³ 12 592 ft3 Total filter volume 1,134 m³ 42 000 ft3 Max. surface load 9.6 m³/m²/h 4 gpm/ft2 The operation of the BAF can be combined in several ways: 1. Nitrification/denitrification in all filters 2. Nitrification/denitrification in 5 filters, post-denitrification in 1 filter 3. Bottom aeration with full nitrification in all filters 4. Controlled oxygen set-point with simultaneous nitrification/denitrification in all filters. The AS is equipped with a multi-channel on-line meter for the parameters NO , NO , NH and 3 2 4 PO . An oxygen meter is furthermore mounted in the aeration tank. The measuring results are 4 used for control of dissolved oxygen in the aeration tank and for addition of an external car- bon source such as methanol to the anoxic tank. Similar to AS, the BAF is equipped with separate on-line meters for measurement of NH and 4 NO as well as oxygen meters in the filters. The sensor results are used partly for control of 3 , the oxygen set-point and partly for adding an external carbon source to the post- denitrification filter. A laboratory is installed at the treatment plant for sampling and qualita- tive analyses of all the parameters required in relation to wastewater and sludge. The labora- tory is in charge of and responsible for the day-to-day control of operation. TREATMENT PERFORMANCE The average diurnal load and the substance reduction in the ten years since startup of parallel operation in 1995 in the respective plants appear from table 2 below. On the average, the AS plant takes 40 % of the total incoming load, but its flow is increased by 25 % with the liquors summarized in Table 1 above: Copyright © 2006 Water Environment Foundation. All Rights Reserved 165 WEFTEC®.06 Table 2: Year Average Load and Removals from 1995 to 2005 _____________________ BAF AS Inlet flow 4,1 mio. m3 Inlet flow 2,8 mio. m3 Inlet TN 142 ton/year Inlet TN 105 ton/year Inlet TP 17,4 ton/year Inlet TP 12,7 ton/year Outlet TN 63 ton/year Outlet TN 19 ton/year Outlet TP 6,9 ton/year Outlet TP 2,2 ton/year Removal TN 55.6 % Removal TN 82 % Removal TP 60 % Removal TP 83 % The effluent quality is summarised in Fig. 2 for COD and Fig. 4 for TSS and BOD and shows: - COD is slightly lower for AS (up to 10 mg/l), through dilution by backwash water - similarly, final BOD is slightly lower for AS than for BAF - the final TSS are lower and more stable for BAF than AS - On average, all TSS and BOD effluent values are less than 10 mg/l These facts are also confirmed for the ten year average, as illustrated in Table 3. Table 3: Outlet concentration 1995 – 2005 ___________________________________ BAF AS TN 8,7 mg/l TN 7,12 mg/l TP 1,55 mg/l TP 0,79 mg/l COD 58 mg/l COD 49 mg/l BOD 9,5 mg/l BOD 5,9 mg/l For nitrogen, Fig. 5 summarizes the settled influent and effluent yearly averages and shows: - Influent TN is around 40 mg TN/l for an ammonia concentration of 25 mg TN/l - C/N Ratio (Fig. 3) is around 6.5 - BAF Ammonia is lower than the AS ammonia - BAF nitrates are higher than the AS nitrates - BAF TN is slightly higher than the AS TN Overall, the BAF has a slightly lower and more stable ammonia effluent residual averaging 0,5 mg NH4/l, even though the empty bed contact time in the filter bed averages about 1 h (and a real HRT of much less once the space occupied by media, biofilm and air is consid- ered: Tschui et al, 1992). Copyright © 2006 Water Environment Foundation. All Rights Reserved 166 WEFTEC®.06 In contrast, the AS effluent residual ammonia with temperatures near 10 deg C is close to 1 mg N-NH/l or higher, even though the hydraulic retention time is always above 5 h in the bioreactors, and almost twice as high if the clarifiers are included. Because the ammonia is higher in the AS, its nitrate concentration has to be tighter controlled. Therefore the methanol dose is kept slightly higher in the AS, so that the TN in the AS is lower than the total plant requirement. As the total nitrogen in the BAF effluent is slightly higher, the required yearly average of 8 mg TN/l is obtained in the blend of effluents. This difference in nitrification performance is most visible at low temperature, where BAF is much more stable. The latter is shown on Fig. 6, where monthly sewage temperatures are shown for the ten year period, with a yearly range between 8 and 18 deg C and yearly average temperature around 12 deg C. Peaks of 5 mg N-NH4/l or higher can be observed in the AS effluent almost every winter, whereas the peaks for BAF effluent are fewer and less pro- nounced. The lower sensitivity of biofilm reactors to temperature variations has been well documented in pilot tests, where diffusion is the limiting factor (Tschui et al.). For phosphorus, the primary settled effluent after ferric addition has a concentration around 5 mg TP/l, of which less than half is soluble orthophospates, as shown on Fig.7. The filtration and biological uptake in the BAF reduces phosphorus to between 2 mg TP/l and 1.5 mg TP/l, which is mostly soluble ortho-P. A polishing dosage of ferric chloride is introduced into the AS, which lowers the TP in the clarifier effluent to less than 1 mg TP/l. Despite the addition of coagulant into the process, the solids concentration is higher in the AS, and orthophospho- rus are about half of the TP. It is possible to also inject ferric salts into the BAF (Goncalves et al.), and recent tests in Frederikshavn have demonstrated that it is a feasible alternative. OPERATING EXPERIENCE AND COST A calculation of the primary operating costs was made for the respective plants on the basis of the recorded operating data, as shown in Table 4. The cost estimate does not include return on and depreciation of fixed investments as it is not possible to estimate an intrinsic value of the activated sludge plant, which has been built and rebuilt over a long period of time. A com- parison between the construction costs for the two plants would therefore to a great extent be based on a non-documentable assumptions. However, for the extension of the WWTP, an estimate was set up of the costs of upgrading the existing activated sludge plant compared to a BAF addition. These estimates indicated that equivalent additional AS capacity would mean an increased cost of 10-15% compared to the installation of a BAF unit, not counting the additional flexibility that the new process al- lowed, and the difficulty to find suitable area. Inclusion of costs for return on and depreciation of the fixed investment in Frederikshavn would therefore be in favor of the installation of the BAF. Initially, the operation cost between the two systems was rather similar, the higher power cost of BAF offset by the FeCl3 consumption and more manpower needs for activated sludge. The implementation of the STAR automatic control system allowed to regulate the aeration tank blowers through measuring oxygen and the nitrate content. Furthermore, the change in back- wash water returns, sending all BAF backwash directly to the AS tanks has improved the C/N ratio there, reducing the need for external carbon and methanol consumption considerably. Copyright © 2006 Water Environment Foundation. All Rights Reserved 167 WEFTEC®.06 Table 4: Yearly average consumption over the last ten years BAF AS 1051 Mwh/year 423 Mwh /year 0,26 kWh /m3 0,15 kWh/m3 Staff / year 450 hour Staff / year 400 hour Extern carbon 97 ton/year Extern carbon 94 ton/year FeCl 0 ton/year FeCl 30 ton/year 3 3 Staff : 38 $ US / hour Extern Carbon 0,17 $ US / kg FeCl 173 $ US / ton Power consumption 0,11 $ US/kwH 3 As a result, the operation cost of AS from 1999 on were lowered drastically, to almost 30 % of its previous level, mainly by cutting power consumption and manpower needs. Extending the controls to the BAF system in 2000 brought the cost in balance again, with the BAF con- suming relatively 50 % more energy, and the AS using relatively more methanol and man- power. For only 40 % of the influent flow in the AS, the carbon dosage and manpower re- quirements are only slightly lower than for BAF. As shown on Fig. 8, the total energy consumption of the plant, with all influent and effluent pumping and the solids handling, is around 0.4 kwh/m3. The biological treatment consumes around 0.25 kwH/m3 for the BAF and 0.15 kwH/m3 for AS. If the specific flow per Popula- tion Equivalent is considered for 200 l/PE, the figures with 11 Kwh/PE/yr for AS and 18 Kwh/PE/yr for BAF are on the lower end of the benchmarking figures in Germany, where the MURL (1999) states an energy demand for the activated sludge of approx. 16 to 29 kWh/PE/yr. The chemical dosages of Ferric in Primary and AS, and Methanol in the bioreactors are shown in Fig. 9. The Ferric dose in the Primary tank is stabilised around 20 mg/l, with a fur- ther 5 mg/l introduced in the AS. The methanol dose is optimised around 30 mg Me/l in the AS, with 10 mg/l less in BAF. After optimisation with automatic controls in 2000, the operating cost averages around 0.036 $/m3 for BAF and 0.028 $/m3 for AS, not counting the Ferric cost, or about 25 % lower. Relative to the nitrogen reduction, the specific cost correspond to 1.9 $ US/kg TN in the BAF and 0.9 $ US/kg TN in the AS. Copyright © 2006 Water Environment Foundation. All Rights Reserved 168 WEFTEC®.06 CONCLUSIONS By comparing two treatment systems on full scale for ten years, both conventional AS as well as BAF are operationally reliable and easy to handle and maintain. Because of anaerobic zones and FeCl3 addition, the AS has a better reduction of Phosphorus than the BAF, which on the other hand is less sensitive to fluctuations in both hydraulic and pollution load. The BAF also maintains a better and more stable nitrification than the activated sludge plant, par- ticularly at low wastewater temperatures. Under comparable conditions, the operating costs of the units in Frederikshavn are similar relative to each m³ of treated wastewater (0,03 $ US/m3) or per kg removed nitrogen (0,7 $ US/kg), with an advantage to AS for energy. When including the construction costs it would, however, be to the advantage of the BAF unit. The implementation of an advanced control system in both AS and BAF has contributed to considerable operational cost reductions. In addition, a better and more reliable operation during rain peaks can be obtained by chang- ing the control strategy for the entire plant, changing the post-denitrification filter at the BAF and returning the sludge liquor from the BAF to the AS. The BAF allows to accept a wet weather load of up to 6 times dry weather average flow, almost eliminating any untreated CSO discharges into the estuary. REFERENCES Goncalves, RF, Sammut, F, and Rogalla, F (1992 b) High Rate Biofilters – Simultaneous P- Precipitation and Nitrogen Removal, in Chemical Treatment III, H.Hahn and H.Oedegaard (Eds.), Springer ,NY Rogalla F., Badard M., Hansen F. and Dansholm P. (1992): Upscaling a Compact Nitrogen Process. Wat. Sci Tech. 26, (5/6), 1067-1076. MURL NRW (Ministry of the Environnement of the State of North-Rhine Westphalia): Energie in Kläranlagen – Energy in Wastewater Treatment Plants, Handbuch, 1. Auflage, September 1999 Nielsen M.K., Lynggaard-Jensen A. (1993). Superior Tuning And Reporting (STAR) - A new concept for on-line process control of wastewater treatment plants. IAWQ ICA workshop 1993, Hamilton, Canada. Soerensen, J., Thornberg, D.E. and Nielsen, M.K. (1994). Optimisation of a Nitrogen Removing Biological Wastewater Treatment Plant using On-line Measurements. WEF Research Journal, 66 (3), 236-242. Thornberg, D. E., Nielsen, M. K., and Andersen, K. L.(1993). Nutrient removal: On-line measurements and control strategies. Wat. Sci. Tech. 28. , (11-12), 549-560. Tschui, M., Boller, M., Gujer, W., Eugster, J., Mader C., and Stengel, C (1992). Tertiary nitrification in aerated pilot biofilters, Wat. Sci. Tech. 29, (10-11), 23-32 Copyright © 2006 Water Environment Foundation. All Rights Reserved 169 WEFTEC®.06 300 290 280 COD CODfilt SS BOD BAF COD AS COD 270 260 250 240 230 220 210 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 Figure 2: COD, COD filt, BOD and TSS in Primary Effluent and Final COD (mg/l) of BAF and AS 140 120 100 80 60 40 20 0 1995 1997 1999 2001 2003 2005 Flow BAF/AS BAF Recirculation CSO Bypass Design Flow BW as % of BAF Flow Figure 3: Relative Flows – Influent vs. Design (of 16 500 m3/d), Untreated Wet Weather Bypass, BAF vs. AS, BAF Recirculation vs. Influent, and % BW of BAF Flow Copyright © 2006 Water Environment Foundation. All Rights Reserved 170 WEFTEC®.06 12.5 10.5 C/N IN Ratio BAF SS BAF BOD AS SS AS BOD 8.5 6.5 4.5 2.5 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 Figure 4: Primary Settled C/N Ratio and Final Effluent BOD and TSS (mg/l) for AS and BAF 50 45 40 Tot-N 35 NH4 BAF TN 30 BAF NH4 25 BAF NO3 20 AS TN 15 AS NH4 AS NO3 10 5 0 1994 1996 1998 2000 2002 2004 2006 Figure 5: Total Nitrogen, Ammonia and Nitrate - Yearly Averages (mg/l) for BAF and AS Copyright © 2006 Water Environment Foundation. All Rights Reserved 171

Description:
The Wastewater Treatment Plant (WWTP) of Frederikshavn, Denmark, was extended in the stormwater bypass to the BAF and switching all six BAF to full nitrification. the existing activated sludge plant, in order to avoid the large additional
See more

The list of books you might like

Most books are stored in the elastic cloud where traffic is expensive. For this reason, we have a limit on daily download.