CHAPTER 29 WATER SUPPLY AND DISTRIBUTION ASSE 1035, ASSE 1052, CSA CAN/CSA B64.2, CSA SECTION P2901 CAN/CSAB64.2.2,CSAB64.7.Thesedevicesshalloper- GENERAL ate under normal atmospheric pressure when the critical P2901.1Potablewaterrequired.Dwellingunitsshallbepro- level is installed at the required height. videdwithasupplyofpotablewaterintheamountsandpres- sures specified in this chapter. In a building where both a P2902.2.3Backflowpreventerwithintermediateatmo- potableandnonpotablewater-distributionsystemareinstalled, sphericvent.Backflowpreventerswithintermediateatmo- eachsystemshallbeidentifiedbycolormarking,metaltagor spheric vents shall conform to ASSE 1012 or CSA otherappropriatemethod.Anynonpotableoutletthatcouldin- CAN/CSAB64.3.Thesedevicesshallbepermittedtobein- advertentlybeusedfordrinkingordomesticpurposesshallbe stalled where subject to continuous pressure conditions. posted. The reliefopening shalldischarge by airgap and shallbe prevented from being submerged. P2902.2.4 Pressure-type vacuum breakers. Pres- SECTION P2902 sure-type vacuum breakers shall conform to ASSE 1020 PROTECTION OF POTABLE WATER SUPPLY andspill-proof vacuumbreakersshallcomplywithASSE P2902.1General.Apotablewatersupplysystemshallbede- 1056.Thesedevicesaredesignedforinstallationundercon- signedandinstalledinsuchamannerastopreventcontamina- tinuous pressure conditions when the critical level is in- tionfromnonpotableliquids,solidsorgasesbeingintroduced stalled at the required height. Pressure-type vacuum intothepotablewatersupply.Connectionsshallnotbemadeto breakers shall not be installed in locations where spillage apotablewatersupplyinamannerthatcouldcontaminatethe could cause damage to the structure. watersupplyorprovideacross-connectionbetweenthesupply P2902.2.5 Reduced pressure principle backflow andsourceofcontaminationunlessanapprovedbackflow-pre- preventer. Reduced pressure principle backflow ventiondeviceisprovided.Cross-connectionsbetweenanin- preventersshallconformtoASSE1013,AWWAC511or dividualwatersupplyandapotablepublicwatersupplyshall CSACAN/CSAB64.4.Reducedpressuredetectorassem- beprohibited,exceptwhereanappropriatecrosscontrolcon- bly backflow preventers shall conform to ASSE 1047. nectiondeviceisinstalledinaccordancewithSubpart5-1.31of Thesedevicesarepermittedtobeinstalledwheresubject the New York State Sanitary Code (10NYCRR). to continuous pressure conditions. The relief opening P2902.2Backflowprotection.Ameansofprotectionagainst shalldischargebyairgapandshallbepreventedfrombe- backflow shall be provided in accordance with Sections ingsubmerged. P2902.2.1 through P2902.2.6. Backflow prevention applica- P2902.2.6Doublecheckvalveassemblies.Doublecheck tions shall conform to Table P2902.2, except as specifically valve assembliesshall conform to ASSE 1015 or AWWA stated in Sections P2902.2 through P2902.4. C510. Double-detector check valve assemblies shall con- On-sitecontainmentinconformancewithSubpart5-1.31of formtoASSE1048.Thesedevicesshallbecapableofoper- the New York State Sanitary Code (10 NYCRR) may be re- ation under continuous pressure. quiredbytheproviderofpublicwater,dependingonthedegree ofhazard,toprotectpublicwatersystemsthrough theuseof P2902.3Protectionofpotablewateroutlets.Allpotablewa- appropriatebackflowprevention device installations. ter openings and outlets shall be protected by an air gap, re- ducedpressureprinciplebackflowpreventerwithatmospheric P2902.2.1 Air gaps. Air gaps shall comply with ASME vent,atmospheric-typevacuumbreaker,pressure-typevacuum A112.1.2 and air gap fittings shall comply with ASME breaker or hose connectionbackflowpreventer. A112.1.3. The minimum air gap shall be measured verti- cally from the lowest end of a water supply outlet to the P2902.3.1Fillvalves.Flushtanksshallbeequippedwithan floodlevelrimofthefixtureorreceptorintowhichsuchpo- antisiphon fill valve conforming to ASSE 1002 or CSA tablewateroutletsdischarge.Theminimumrequiredairgap B125.Thefillvalvebackflowpreventershallbelocatedat shallbetwicethediameteroftheeffectiveopening ofthe least1inch(25.4mm)abovethefullopeningoftheover- outlet,butinnocaselessthanthevaluesspecifiedinTable flow pipe. P2902.2.1.Anairgapisrequiredatthedischargepointofa P2902.3.2 Deck-mounted and integral vacuum break- reliefvalveorpiping.Airgapdevicesshallbeincorporated ers.Approveddeck-mountedvacuumbreakersandfaucets in dishwashing and clothes washing appliances. with integral atmospheric or spill-proof vacuum breakers P2902.2.2Atmospheric-typevacuumbreakers.Pipe-ap- shallbeinstalledinaccordancewiththemanufacturer’sin- plied atmospheric-type vacuum breakers shall conform to stallation instructions and the requirements for labeling ASSE1001orCSACAN/CSAB64.1.1.Hoseconnection withthecriticallevelnotlessthan1inch(25.4mm)above vacuumbreakersshallconformtoASSE1011,ASSE1019, the flood level rim. RESIDENTIAL CODE OF NEW YORK STATE 381 WATER SUPPLY AND DISTRIBUTION TABLE P2902.2 APPLICATION FORBACKFLOWPREVENTERS DEGREE OF APPLICABLE DEVICE HAZARDa APPLICATIONb STANDARDS Air gap High or low hazard Backsiphonageorbackpressure ASME A112.1.2 Air gap fittings for use with plumbing fixtures, High or low hazard Backsiphonageorbackpressure ASME A112.1.3 appliances and appurtenances Antisiphon-typefill valves for gravity water closet ASSE1002 High hazard Backsiphonageonly flush tanks CSACAN/CSAB125 Backflowpreventerwith intermediate atmospheric Backpressureorbacksiphonage ASSE1012 Low hazard vents Sizes1/ ″–3/ ″ CSACAN/CSA-B64.3 4 4 Double checkbackflowprevention assembly and Backpressureorbacksiphonage ASSE1015 double check fire protectionbackflowprevention Low hazard Sizes3/ ″– 16″ AWWAC510 assembly 8 Backpressureorbacksiphonage Double check detector fire protectionbackflow Low hazard (Fire sprinkler systems) ASSE1048 prevention assemblies Sizes 2″– 16″ Backpressureorbacksiphonage Dual-check-valve-typebackflowpreventer Low hazard ASSE1024 Sizes1/ ″– 1″ 4 Lowheadbackpressure,ratedworking Hose connectionbackflowpreventer High or low hazard pressurebackpressureorbacksiphonage ASSE1052 Sizes1/ ″–1″ 2 Lowheadbackpressureorbacksiphonage ASSE1011 Hose-connection vacuum breaker High or low hazard Sizes1/ ″,3/ ″, 1″ CSACAN/CSA-B64.2 2 4 Laboratory faucetbackflowpreventer High or low hazard Lowheadbackpressureandbacksiphonage ASSE1035,CSAB64.7 Backsiphonageonly ASSE1001 Pipe-applied atmospheric-type vacuum breaker High or low hazard Sizes1/ ″– 4″ CSACAN/CSA-B64.1.1 4 Backsiphonageonly Pressure vacuum breaker assembly High or low hazard ASSE1020 Sizes1/ ″– 2″ 2 Reduced pressure detector fire protectionbackflow Backsiphonageorbackpressure High or low hazard ASSE1047 prevention assemblies (Fire sprinkler systems) Reduced pressure principlebackflowpreventerand ASSE1013 Backpressureorbacksiphonage reduced pressure principle fire protectionbackflow High or low hazard Sizes3/ ″- 16″ AWWAC511 preventer 8 CSACAN/CSAB64.4 Backsiphonageonly Spillproofvacuum breaker High or low hazard ASSE1056 Sizes1/ ″- 2″ 4 ASSE1019 Vacuum breaker wall hydrants, frost-resistant, Low headbackpressureor automatic draining type High or low hazard backsiphonageSizes3/ ″, 1″ CSA 4 CAN/CSA-B64.2.2 For SI: 1 inch = 25.4 mm. a. Low hazard—See Pollution (Section 202). High hazard—See Contamination (Section 202). b. SeeBackpressure(Section 202). SeeBackpressure, Low Head (Section 202). SeeBacksiphonage(Section 202). P2902.3.3 Hose connection. Sillcocks, hose bibbs, wall chines where backflow prevention is otherwise hydrantsandotheropeningswithahoseconnectionshallbe provided or is integral with the machine. protectedbyanatmospheric-typeorpressure-typevacuum P2902.4 Protectionofpotablewaterconnections.Allcon- breakerorapermanentlyattachedhoseconnectionvacuum nections to the potable water shall conform to Sections breaker. P2902.4.1 through P2902.4.5. Exceptions: P2902.4.1 Connections to boilers.Thepotablesupply to theboilershallbeequippedwithabackflowpreventerwith 1. This section shall not apply to water heater and an intermediate atmospheric vent complying with ASSE boiler drain valves that are provided with hose 1012orCSACAN/CSAB64.3.Whereconditioningchemi- connectionthreadsandthatareintendedonlyfor calsareintroducedintothesystem,thepotablewatercon- tank or vessel draining. nectionshallbeprotectedbyanairgaporareducedpressure 2. Thissectionshallnotapplytowatersupplyvalves principlebackflowpreventercomplyingwithASSE1013, intended for connection of clothes washing ma- CSACAN/CSAB64.3 orAWWAC511. 382 RESIDENTIAL CODE OF NEW YORK STATE WATER SUPPLY AND DISTRIBUTION P2902.4.2Heatexchangers.Heatexchangersutilizingan mand,thecapacitiesatthepointofoutletdischargeshallnotbe essentially toxic transfer fluid shall be separated from the lessthanshowninTableP2903.1.Thereshallbeadequatepro- potablewaterbydouble-wallconstruction.Anairgapopen visiontodrainthewatersystem.Theuseofcompressedairto totheatmosphereshallbeprovidedbetweenthetwowalls. drainthewatersystemshallbeconsideredanadequateprovi- Heat exchangers utilizing an essentially nontoxic transfer sion. fluid shall bepermitted to be of single-wall construction. P2903.1.1DisinfectionofPotableWaterSystem. Newor P2902.4.3 Lawn irrigation systems. The potable water repairedpotablewatersystemsshallbepurgedofdeleteri- supplytolawnirrigationsystemsshallbeprotectedagainst ousmatteranddisinfectedpriortoutilization. Themethod backflow by an atmospheric-type vacuum breaker, a to be followed shall be in accordance with the applicable pressure-typevacuumbreakerorareducedpressureprinci- New York State Department of Health regulations. plebackflowpreventer.Avalveshallnotbeinstalleddown- TABLE P2903.1 stream from an atmospheric vacuum breaker. Where REQUIRED CAPACITIES AT chemicalsareintroducedintothesystem,thepotablewater POINT OF OUTLET DISCHARGE supply shall be protected against backflow by a reduced FLOW pressure principlebackflowpreventer. FLOW RATE PRESSURE FIXTURE AT POINT OF OUTLET (gpm) (psi) P2902.4.4 Connections to automatic fire sprinkler sys- tems.Thepotablewatersupplytoautomaticfiresprinkler Bathtub 4 8 systems shall be protected against backflow by a double Bidet 2 4 check-valve assembly or a reduced pressure principle backflowpreventer. Dishwasher 2.75 8 Exception:Wheresystemsareinstalledasaportionof Laundry tub 4 8 thewaterdistributionsysteminaccordancewiththere- quirementsofthiscodeandarenotprovidedwithafire Lavatory 2 8 departmentconnection,isolationofthewatersupplysys- For SI: 1 gallon per minute = 3.785 L/m, tem shall not be required. 1 pound per square inch = 6.895kPa. P2902.4.4.1 Additives or nonpotable source. Where P2903.2Maximumflowandwaterconsumption.Themaxi- systems contain chemical additives or antifreeze, or mum water consumption flow rates and quantities for all wheresystemsareconnectedtoanonpotablesecondary plumbing fixtures and fixture fittings shall be in accordance watersupply,thepotablewatersupplyshallbeprotected with Table P2903.2. against backflow by a reduced pressure principle backflow preventer. Where chemical additives or anti- TABLE P2903.2 freeze is added to only a portion of an automatic fire MAXIMUM FLOW RATES AND CONSUMPTION FOR sprinklerorstandpipesystem,thereducedpressureprin- PLUMBING FIXTURES AND FIXTUREFITTINGSb ciplebackflowpreventershallbepermittedtobelocated PLUMBING FIXTURE PLUMBING FIXTURE so as to isolate that portion of the system. OR FIXTURE FITTING OR FIXTURE FITTING P2902.4.5Solarsystems.Thepotablewatersupplytoaso- Lavatory faucet 2.2gpmat 60 psi larsystemshallbeequippedwithabackflowpreventerwith Showerheada 2.5gpmat 80 psi intermediateatmosphericventcomplyingwithASSE1012 orareducedpressureprinciplebackflowpreventercomply- Sink faucet 2.2gpmat 60 psi ingwithASSE1013.Wherechemicalsareutilized,thepo- Water closet 1.6 gallons per flushing cycle tablewatersupplyshallbeprotectedbyareducedpressure principlebackflowpreventer. For SI: 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895kPa. Exception:Whereallsolarsystempipingisapartofthe a. A handheld shower spray is also a shower head. potablewaterdistributionsystem,inaccordancewiththe b. Consumption tolerances shall be determined from referenced standards. requirementsofthePlumbing CodeofNewYorkState, andallcomponentsofthepipingsystemarelistedforpo- P2903.3 Minimum pressure. Minimum static pressure (as table water use, cross-connection protection measure determined by the local water authority) at the building en- shall not be required. tranceforeitherpublicorprivatewaterserviceshallbe40psi (276kPa). P2902.5Access.Allbackflowpreventiondevicesshallbeac- cessible for inspection and servicing. P2903.3.1 Maximum pressure. Maximum static pressure shallbe80psi(551kPa).Whenmainpressureexceeds80psi (551kPa),anapprovedpressure-reducingvalveconforming SECTION P2903 toASSE1003shallbeinstalledonthedomesticwaterbranch WATER-SUPPLY SYSTEM mainorriserattheconnectiontothewater-servicepipe. P2903.1Watersupplysystemdesigncriteria.Thewaterser- P2903.4Thermalexpansion.Inadditiontotherequiredpres- viceandwaterdistributionsystemsshallbedesignedandpipe sure relief valve, an approved device for thermal expansion sizesshallbeselectedsuchthatunderconditionsofpeakde- controlshallbeinstalledonanywatersupplysystemutilizing RESIDENTIAL CODE OF NEW YORK STATE 383 WATER SUPPLY AND DISTRIBUTION storagewaterheatingequipmentwheneverthebuildingsupply ter-hammer arrestors shall be installed in accordance with pressureexceedsthepressure-reducingvalvesettingorwhen manufacturers’ specifications. Water-hammer arrestors shall any device, such as a pressure-reducing valve, backflow conform toASSE1010. preventerorcheckvalve,isinstalledthatpreventspressurere- P2903.6 Determining water-supply fixture units. Supply liefthroughthebuildingsupply.Thethermalexpansioncontrol loadsinthebuildingwater-distributionsystemshallbedeter- deviceshallbesizedinaccordancewiththemanufacturer’sin- mined by total load on the pipe being sized, in terms of wa- stallation instructions. ter-supplyfixtureunits(w.s.f.u.),asshowninTableP2903.6, P2903.5Waterhammer.Theflowvelocityofthewaterdistri- andgallonperminute(gpm)flowrates[seeTable2903.6(1)]. bution systemshallbe controlled toreduce thepossibilityof Forfixturesnotlisted,chooseaw.s.f.u.valueofafixturewith water hammer. A water-hammer arrestor shall be installed similar flow characteristics. where quick-closing valves (see definition) are utilized. Wa- TABLE P2903.6 WATER-SUPPLY FIXTURE-UNIT VALUES FOR VARIOUS PLUMBING FIXTURES AND FIXTURE GROUPS WATER-SUPPLY FIXTURE-UNIT VALUE (w.s.f.u.) TYPE OF FIXTURES OR GROUP OF FIXTURES Hot Cold Combined Bathtub (with/without overhead shower head) 1.0 1.0 1.4 Clothes washer 1.0 1.0 1.4 Dishwasher 1.4 — 1.4 Hosebibb(sillcock)a — 2.5 2.5 Kitchen sink 1.0 1.0 1.4 Laundry tub 1.0 1.0 1.4 Lavatory 0.5 0.5 0.7 Shower stall 1.0 1.0 1.4 Water closet (tank type) — 2.2 2.2 Full-bath group with bathtub (with/without 1.5 2.7 3.6 shower head) or shower stall Half-bath group (water closet and lavatory) 0.5 2.5 2.6 Kitchen group (dishwasher and sink 1.9 1.0 2.5 with/without garbage grinder) Laundry group (clothes washer standpipe and 1.8 1.8 2.5 laundry tub) For SI: 1 gallon per minute = 3.785 L/m. a. Thefixtureunitvalue2.5assumesaflowdemandof2.5gpm,suchasforanindividuallawnsprinklerdevice.Ifahosebibb/sillcockwillberequiredtofurnisha greater flow rate, the equivalent fixture-unit value may be obtained from Table P2903.6 or Table P2903.7. 384 RESIDENTIAL CODE OF NEW YORK STATE WATER SUPPLY AND DISTRIBUTION TABLE P2903.6(1) CONVERSIONS FROM WATER SUPPLY FIXTURE UNIT TO GALLON PER MINUTE FLOW RATES SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS SUPPLY SYSTEM PREDOMINANTLY FOR FLUSH VALVES Load Demand Load Demand (Water supply (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) fixture units) (Gallons per minute) (Cubic feet per minute) 1 3.0 0.04104 — — — 2 5.0 0.0684 — — — 3 6.5 0.86892 — — — 4 8.0 1.06944 — — — 5 9.4 1.256592 5 15.0 2.0052 6 10.7 1.430376 6 17.4 2.326032 7 11.8 1.577424 7 19.8 2.646364 8 12.8 1.711104 8 22.2 2.967696 9 13.7 1.831416 9 24.6 3.288528 10 14.6 1.951728 10 27.0 3.60936 11 15.4 2.058672 11 27.8 3.716304 12 16.0 2.13888 12 28.6 3.823248 13 16.5 2.20572 13 29.4 3.930192 14 17.0 2.27256 14 30.2 4.037136 15 17.5 2.3394 15 31.0 4.14408 16 18.0 2.90624 16 31.8 4.241024 17 18.4 2.459712 17 32.6 4.357968 18 18.8 2.513184 18 33.4 4.464912 19 19.2 2.566656 19 34.2 4.571856 20 19.6 2.620128 20 35.0 4.6788 25 21.5 2.87412 25 38.0 5.07984 30 23.3 3.114744 30 42.0 5.61356 35 24.9 3.328632 35 44.0 5.88192 40 26.3 3.515784 40 46.0 6.14928 45 27.7 3.702936 45 48.0 6.41664 50 29.1 3.890088 50 50.0 6.684 For SI: 1 gallon per minute = 3.785 L/m, 1 cubic foot per minute = 0.4719 L/s. RESIDENTIAL CODE OF NEW YORK STATE 385 WATER SUPPLY AND DISTRIBUTION P2903.7Sizeofwater-servicemains,branchmainsandris- opedlength”columntoafixtureunitequalto,orgreater ers.Theminimumsizewaterservicepipeshallbe3/ inch(19.1 thanthetotalinstallationdemandcalculatedbyusingthe 4 mm). Thesizeofthewaterservicepipefromapublicsource “combined” water supply fixture unit column of Table shallbedeterminedbytheauthorityregulatingthepublicwater P2903.6.Readthewaterservicepipeandmetersizesin supply. Thesizeofwaterservicemains,branchmainsandris- thefirstleft-handcolumnandthemaindistributionpipe ers shall be determined according to water supply demand to the building in the second left-hand column on the [gpm(L/m)],availablewaterpressure[psi(kPa)]andfriction same row. lossduetothewatermeteranddevelopedlengthofpipe[feet 4. To determine the size of each water distribution pipe, (m)],includingequivalentlengthoffittings. Thesizeofeach startatthemostremoteoutletoneachbranch(eitherhot waterdistributionsystemshallbedeterminedaccordingtothe orcoldbranch)and,workingbacktowardthemaindis- procedureoutlinedinthissectionorChapter6ofthePlumbing tributionpipetothebuilding,addupthewatersupply Code of New York State: fixture unit demand passing through each segment of 1. Obtain the minimum daily static service pressure [psi thedistributionsystemusingtherelatedhotorcoldcol- (kPa)] available (as determined by the local water au- umn of Table P2903.6. Knowing demand, the size of thority)atthewatermeterorothersourceofsupplyatthe each segment shall be read from the second left-hand installation location. Adjust this minimum daily static column of the same table and a maximum developed pressure [psi (kPa)] for the following conditions: lengthcolumnselectedinSteps1and2,underthesame ornextsmallersizemeterrow.Innocasedoesthesize 1.1.Determinethedifferenceinelevationbetweenthe ofanybranchormainneedtobelargerthatthesizeof sourceofsupplyandthehighestwatersupplyout- themaindistributionpipetothebuildingestablishedin let.Wherethehighestwatersupplyoutletislocated Step3. abovethesourceofsupply,deduct0.5psi(3.4kPa) for each foot (0.3 m) of difference in elevation. P2903.8Parallelwater-distributionsystemmanifolds.Hot Wherethehighestwatersupplyoutletislocatedbe- andcoldparallelwater-distributionsystemmanifoldswithin- lowthesourceofsupply,add0.5psi(3.4kPa)for dividualdistributionlinestoeachfixtureorfixturefittingshall eachfoot(0.3m)ofdifferenceinelevation. besizedandinstalledinaccordancewithSectionsP2903.8.1 1.2.Where a water pressure reducing valve is in- through P2903.8.7 stalledinthewaterdistributionsystem,themini- P2903.8.1Sizingofmanifolds.Manifoldsshallbesizedin mum daily static water pressure available is 80 accordancewithTableP2903.8.1.Totalgallonsperminute percentoftheminimumdailystaticwaterpres- is the demand for all outlets. sure at the source of supply or the set pressure downstream of the pressure reducing valve, P2903.8.2Minimumsize.Theminimumsizeofindividual whichever is smaller. distributionlinesshallbe3/ inch(9.5mm).Certainfixtures 8 suchasone-piecewaterclosetsandwhirlpoolbathtubsshall 1.3.Deductallpressurelossesduetospecialequip- requirealargersizewherespecifiedbythemanufacturer.If ment such as a backflow preventer, water filter awaterheaterisfedfromtheendofacoldwatermanifold, and water softener. Pressure loss data for each themanifoldshallbeonesizelargerthanthewaterheater pieceofequipmentshallbeobtainedthroughthe feed. manufacturer of such devices. 1.4.Deduct thepressure inexcessof 8 psi(55 kPa) P2903.8.3Maximumlength.Themaximumlengthofindi- due to installation of the special plumbing fix- vidual distribution lines shall be 60 feet (18 288 mm) ture,suchastemperaturecontrolledshowerand nominal. flushometertank water closet. P2903.8.4Orientation.Manifoldsshallbepermittedtobe Using the resulting minimum available pres- installed in a horizontal or vertical position. sure, find the corresponding pressure range in P2903.8.5Supportandprotection.Plasticpipingbundles Table P2903.7. shallbesecuredinaccordancewiththemanufacturer’sin- 2. Themaximumdevelopedlengthforwaterpipingisthe stallation instructions and supported in accordance with actuallengthofpipebetweenthesourceofsupplyand Section P2605. Bundles that have a change in direction themostremotefixture,includingeitherhot(throughthe equaltoorgreaterthan45degrees(0.79rad)shallbepro- waterheater)orcoldwaterbranchesmultipliedbyafac- tected from chaffing at the point of contact with framing tor of 1.2 to compensate for pressure loss through fit- members by sleeving or wrapping. tings. P2903.8.6Valving.Fixturevalves,wheninstalled,shallbe SelecttheappropriatecolumninTableP2903.7equal locatedeitheratthefixtureoratthemanifold.Ifvalvesare to or greater than the calculated maximum developed installedatthemanifold,theyshallbelabeledindicatingthe length. fixture served. 3. To determine the size of water service pipe, meter and maindistributionpipetothebuildingusingtheappropri- P2903.8.7Hosebibbbleed.Areadilyaccessibleairbleed ate table, follow down the selected “maximum devel- shallbeinstalledinhosebibbsuppliesatthemanifoldorat the hosebibbexit point. 386 RESIDENTIAL CODE OF NEW YORK STATE WATER SUPPLY AND DISTRIBUTION TABLE P2903.7 MINIMUM SIZE OF WATER METERS,MAINS AND DISTRIBUTION PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES Pressure Range—30 to 39 psi METER AND DISTRIBUTION MAXIMUM DEVELOPMENT LENGTH (feet) SERVICE PIPE PIPE (inches) (inches) 40 60 3/ 1/ a 2.5 2 4 2 3/ 3/ 9.5 7.5 4 4 3/ 1 32 25 4 1 1 32 32 3/ 11/ 32 32 4 4 1 11/ 80 80 4 11/ 11/ 80 80 2 4 1 11/ 87 87 2 11/ 11/ 151 151 2 2 Pressure Range—40 to 49 psi METER AND DISTRIBUTION MAXIMUM DEVELOPMENT LENGTH (feet) SERVICE PIPE PIPE (inches) (inches) 40 60 3/ 1/ a 3 2.5 4 2 3/ 3/ 9.5 9.5 4 4 3/ 1 32 32 4 1 1 32 32 3/ 11/ 32 32 4 4 1 11/ 80 80 4 11/ 11/ 80 80 2 4 1 11/ 87 87 2 11/ 11/ 151 151 2 2 Pressure Range—50 to 60 psi METER AND DISTRIBUTION MAXIMUM DEVELOPMENT LENGTH (feet) SERVICE PIPE PIPE (inches) (inches) 40 60 3/ 1/ a 3 3 4 2 3/ 3/ 9.5 9.5 4 4 3/ 1 32 32 4 1 1 32 32 3/ 11/ 32 32 4 4 1 11/ 80 80 4 11/ 11/ 80 80 2 4 1 11/ 87 87 2 11/ 11/ 151 151 2 2 (continued) RESIDENTIAL CODE OF NEW YORK STATE 387 WATER SUPPLY AND DISTRIBUTION TABLE P2903.7—continued MINIMUM SIZE OF WATER METERS,MAINS AND DISTRIBUTION PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES Pressure Range—greater than 60 psi METER AND DISTRIBUTION MAXIMUM DEVELOPMENT LENGTH (feet) SERVICE PIPE PIPE (inches) (inches) 40 60 3/ 1/ a 3 3 4 2 3/ 3/ 9.5 9.5 4 4 3/ 1 32 32 4 1 1 32 32 3/ 11/ 32 32 4 4 1 11/ 80 80 4 11/ 11/ 80 80 2 4 1 11/ 87 87 2 11/ 11/ 151 151 2 2 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa. a. Minimum size for building supply is3/-inch pipe. 4 TABLE P2903.8.1 MANIFOLD SIZING PLASTIC METALLIC Nominal Size ID Maximuma Nominal Size ID Maximuma (inches) gpm (inches) gpm 3/ 17 3/ 11 4 4 1 29 1 20 11/ 46 11/ 31 4 4 11/ 66 11/ 44 2 2 For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 foot per second = 0.3048 m/s. NOTE:See Table P2903.6 for w.s.f.u and Table 2903.6(1) for gallon-per-minute (gpm) flow rates. a. Based on velocity limitation: plastic—12 fps; metal—8 fps. 388 RESIDENTIAL CODE OF NEW YORK STATE WATER SUPPLY AND DISTRIBUTION P2903.9 Valves.Valvesshallbeinstalledinaccordancewith Exception: Frost-proof hose bibbs installed such that the Sections P2903.9.1 through P2903.9.3. stemextends through thebuilding insulationintoanopen heated or semi-conditioned space need not be separately P2903.9.1Servicevalve.Eachdwellingunitshallbepro- valved. (See Figure P2903.10.) vided with an accessible main shutoff valve near the en- tranceofthewaterservice.Thevalveshallbeofafull-open typehavingnominalrestrictiontoflow,withprovisionfor drainagesuchasableedorificeorinstallationofaseparate SECTION P2904 drainvalve.Additionally,thewaterserviceshallbevalved MATERIALS,JOINTS AND CONNECTIONS at the curb or property line in accordance with local requirements. P2904.1Soilandgroundwater.Theinstallationofwaterser- vicepiping,fittings,valves,appurtenancesandgasketsshallbe P2903.9.2 Water heater valve. A readily accessible prohibited insoiland groundwaterthatiscontaminated with full-open valve shall be installed in the cold-water supply solvents,fuels,organiccompoundsorotherdetrimentalmate- pipe to each water heater at or near the water heater. rials that cause permeation, corrosion, degradation or struc- tural failure of the water service material. P2903.9.3Valverequirements.Valvesservingindividual fixtures, appliances, risersand branches shallbe provided P2904.1.1Investigationrequired.Wheredetrimentalcon- withaccess.Anindividualshutoffvalveshallberequiredon ditions are suspected, a chemical analysis of the soil and thefixturesupplypipetoeachplumbingfixtureotherthan groundwater conditions shall be required to ascertain the bathtubs and showers. acceptabilityof the water service materialfor the specific installation. P2903.10Hosebibb.Hosebibbssubjecttofreezing,including the “frost-proof” type, shall be equipped with an accessible P2904.1.2 Detrimental condition. When a detrimental stop-and-waste-typevalveinsidethebuildingsothattheymay condition exists, approved alternate materials or alternate be controlled and/or drained during cold periods. routing shall be required. FIGURE P2903.10 TYPICAL FROST-PROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE RESIDENTIAL CODE OF NEW YORK STATE 389 WATER SUPPLY AND DISTRIBUTION TABLE P2904.4.1 WATER SERVICEPIPEa Acrylonitrile butadiene styrene (ABS) plastic pipe ASTM D 1527; ASTM D 2282 Asbestos-cement pipe ASTM C 296 Brass pipe ASTM B 43 Chlorinated polyvinyl chloride (CPVC) plastic pipe ASTM D 2846; ASTM F 441; ASTM F 442;CSAB137.6 Copper or copper-alloy pipe ASTM B 42; ASTM B 302 Copper or copper-alloy tubing (Type K,WK, L, WL, M orWM) ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 Cross-linked polyethylene/aluminum/cross-linked polyethylene ASTM F 1281;CSACAN/CSAB137.10 (PEX-AL-PEX) pipe Cross-linked polyethylene (PEX) plastic tubing ASTM F 876; ASTM F 877;CSAB137.5 Ductile iron water pipe AWWAC151;AWWAC115 Galvanized steel pipe ASTM A 53 Polybutylene (PB) plastic pipe and tubing ASTM D 2662; ASTM D 2666; ASTM D 3309;CSAB137.8M Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe ASTM F 1282;CSACAN/CSA-B137.9M Polyethylene (PE) plastic pipe ASTM D 2239;CSA-B137.1 Polyethylene (PE) plastic tubing ASTM D 2737;CSAB137.1 Polyvinyl chloride (PVC) plastic pipe ASTM D 1785; ASTM D 2241; ASTM D 2672;CSAB137.3 Stainless steel (Type 304/304L) pipe ASTM A312; ASTM A778 Stainless steel (Type 316/316L) pipe ASTM A312; ASTM A778 P2904.2 Lead content. Pipe and fittings utilized in the wa- P2904.4.2 Water-servicepipeseparationfrombuilding ter-supply system shall have a maximum of 8 percent lead. sewerpipe.Thewater-servicepipeshallbeseparatedfrom thebuildingsewerbyaminimumof5feet(1524mm),mea- P2904.3Polyethyleneplasticpipinginstallation.Polyethyl- sured horizontally, of undisturbed or compacted earth or enepipeshallbecutsquare,usingacutterdesignedforplastic placedonasolidledgeatleast12inches(305mm)above pipe. Except when joined by heat fusion, pipe ends shall be and to one side of the highest point in the sewer line. chamfered toremovesharp edges. Pipethathasbeen kinked P2904.5 Water-distribution pipe. Water-distribution piping shall not be installed. For bends, the installed radius of pipe withindwellingunitsshallconformtoANSI/NSF61andshall curvatureshallbegreaterthan30pipediametersorthecoilra- conform to one of the standards listed in Table P2904.5. All diuswhenbendingwiththecoil.Coiledpipeshallnotbebent hot-water-distributionpipeandtubing shallhaveaminimum beyondstraight.Bendsshallnotbepermittedwithintenpipe pressure rating of 100 psi at 180°F (689 kPaat 82°C). diameters of any fitting or valve. Stiffener inserts used with compression-typefittingsshallnotextendbeyondtheclampor P2904.5.1Underconcreteslabs. Inaccessiblewaterdistribu- nutofthefitting.Flaredjointsshallbepermittedwhererecom- tionpipingunderslabsshallbecopperwatertubeminimum mendedbythemanufacturerandmadebytheuseofatoolde- TypeM,brass,ductileironpressurepipe,cross-linkedpolyeth- signed for that operation. ylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe, chlorinated polyvinyl chloride (CPVC) or P2904.4Waterservicepipe.Waterservicepipeshallconform cross-linkedpolyethylene(PEX)plasticpipeortubing—allto to ANSI/NSF 61 and shall conform to one of the standards be installed with approved fittings or bends. The minimum listed in Table P2904.4.1. Water service pipe or tubing, in- pressureratingforplasticpipeortubinginstalledunderslabs stalledundergroundandoutsideofthestructure,shallhavea shallbe100psiat180°F(689kPaat82°C). minimumworkingpressureratingof160psiat73°F(1100kPa at 23°C). P2904.6Fittings.Pipefittingsshallbeapprovedforinstalla- tionwiththepipingmaterialinstalled,andshallconformtothe P2904.4.1Waterserviceinstallation.Trenching,pipein- respectivepipestandardslistedinTableP2904.6.Pipefittings stallationandbackfillingshallbeinaccordancewithSec- utilized in the water supply system shall also conform to tion P2604. ANSI/NSF 61. 390 RESIDENTIAL CODE OF NEW YORK STATE

Description:
Air gap High or low hazard Backsiphonage or backpressure ASME A112.1.2 Air gap fittings for use with plumbing fixtures, appliances and appurtenances
See more

The list of books you might like

Most books are stored in the elastic cloud where traffic is expensive. For this reason, we have a limit on daily download.